Ecodesign Regulation ( EU ) năm ngoái / 1188 concerning local space heaters does not apply to all application areas. The Regulation applies when an installation is intended to provide thermal comfort for people in the premises. The Regulation does not apply to heating installations of a more technical nature e. g. in engineering / utility rooms, in production processes, frost protection, etc. The Regulation also does not apply to installations in vehicles, offshore or outdoors. Many of Frisco’s products can be used as both local space heaters ( as defined in ( EU ) năm ngoái / 1188 ) and for technical heating purposes. It is up to the installer responsible for the installation to assess whether the Ecodesign Regulation is applicable or not. Control solutions for installations not covered by the Ecodesign Regulation are listed in a separate table .

Controls for installations not covered by the Ecodesign Regulation (EU) 2015/1188

Protection class: IP44.

Note: Remove the two internal fuses 6.3A in the slave units.

Bạn đang đọc: puravent Panther SE12N 6-15 kW wall mounted fan heater Instructions – Manuals+

Control options for installations not covered by the Ecodesign Regulation (EU) 2015/1188

General Instructions

Read these instructions carefully before installation and use. Keep this manual for future reference. The product may only be used as set out in the assembly and operating instructions. The guarantee is only valid if the product is used in the manner intended and in accordance with the instructions .

Application area

Panther 6-15 is a range of very quiet and efficient fan heaters for stationary use. They are intended for heating and drying in e. g. workshops, sports halls, shops, assembly rooms, and drying rooms. Protection class : IP44 .

Mounting

The fan heater is mounted on a wall with a bracket, which allows the direction of the air stream in several directions, straight ahead, to the left, to the right, and down .

Note: The minimum distances given in fig. 2 and 3 must be kept. The fan heaters must not be mounted on the ceiling.

Electrical installation

The electrical installation should be carried out by a qualified electrician in conformity with prevailing regulations. The appliance ] should be preceded by an all-pole switch with at least 3 mm breaking gap. There are several ways to connect depending on the desired function. On delivery, the appliance is equipped with connections on the terminal block .

Factory setting

On delivery, the external thermostat controls heat on/off. In operation, fan and output steps are set on the control box PP15N. With a connection between terminals 14 and
15, the fan RPM will be controlled by the regulation and the heat by the thermostat. Without the connection, the thermostat will control both fan RPM and heat. When accessories are connected or when several heaters are connected to each other and controlled by a common accessory. Between terminals 1 and 13, a 230V~ alarm signal can be obtained. When the temperature limiter is triggered, the voltage will drop to zero. On delivery, the Panther 6 – 15 fan heaters are for 400V3N~. SE135N can be connected to both 440V3~ and 500V3~.

On the back of the appliance, there are knockouts. Cable-glands used must guarantee the protection class requirements! When several heaters are connected to each other and controlled by a common accessory it should be stated in the group center that “The fan heaters are fed from more than one group supply”.

Control

When using this product as a local space heater according to Eco-design Regulation ( EU ) năm ngoái / 1188, it must be supplemented with one of the following approved controls .PP15N, control box and TAP16R, electronicthermostat that include :The product can be controlled in a different way, e. g. by an overall control system ( BMS ), but in that case, the responsibility lies with the installer to ensure that the control system is programmed to make the installation meet the requirements of Ecodesign Regulation ( EU ) năm ngoái / 1188 .

Start-up

When the unit is used for the first time or after a long period of disuse, smoke or odor may result from dust or dirt that has collected on the element. This is completely normal and disappears after a short time .

Overheating
If the temperature limiter has been triggered due to overheating, reset as follows:

Residual current circuit breaker

When the installation is protected by means of a residual current circuit breaker, which trips when the appliance is connected, this may be due to moisture in the heating element. When an appliance containing a heater element has not been used for a long period or stored in a damp environment, moisture can enter the element. This should not be seen as a fault but is simply rectified by connecting the appliance to the main supply via a socket without a safety cut-out, so that the moisture can be eliminated from the element. The drying time can vary from a few hours to a few days. As a preventive measure, the unit should occasionally be run for a short time when it is not being used for extended periods of time .

Packaging

Handling of product at end of working life

This product may contain substances necessary for the functionality of the product but potentially dangerous for the environment. The product should not be disposed of mixed with general household waste but delivered to a designated collection point for environmental recycling. Please contact localauthority for further details of your nearest designated collection point. Recycling of used products saves earth’s resources and reducesglobal footprint .

CAUTION: Some parts of this product can become very hot and cause burns. Particular attention has to be given where children and vulnerable people are present.