Problem |
Possible Cause |
What To Do |
Dehumidifier does not start |
The dehumidifier is unplugged. |
Makes sure the dehumidifier’s plug is pushed completely into the outlet. |
The fuse is blown/circuit breaker is tripped. |
Check the house fuse/circuit breaker box and replace the fuse or reset the breaker. |
Dehumidifier has reached its set humidity level or bucket is full. |
The dehumidifier automatically turns off when either condition occurs. Change to a lower setting or empty the bucket and replace properly. |
Bucket is not in the proper position. |
The bucket must be in place and securely seated for the dehumidifier to operate. |
Power Failure. |
There is a protective time delay (up to 3 minutes) to prevent tripping of the compressor overload. For this reason, the unit may not start normal dehumidification for 3 minutes after itturned back on . |
Dehumidifier does not dry the air as it should |
Did not allow enough time to remove the moisture. |
When first installed, allow at least 24 hours to maintain the desired dryness. |
Airflow is restricted. |
Make sure there are no curtains, blinds or furniture blocking the top or back of the dehumidifier. See the Choosing a Location section. |
Dirty Filter |
See the Care and Cleaning section. |
The Humidity Control may not be set low enough. |
For drier air, press the ź pad and set to a lower percent value (%) or at the Nonstop setting for maximum dehumidification. |
Doors and windows may not be closed tightly. |
Check that all doors, windows and other openings are securely closed. |
Clothes dryer may be blowing moisure-laden air into the room. |
Install the dehumidifier away from the dyer. The dryer should be vented to the outside. |
Room temperature is too low. |
Moisture removal is best at higher room temperatures. Lower room temperatures will reduce the moisture removal rate. Models are designed to be operated at temperatures above 41°F (5°C). |
Dehumidifier runs too much |
Area to be dehumidified is too large. |
The capacity of your dehumidifier may not be adequate. |
Doors and windows are open. |
Close all doors and windows to the outside. |
Frost appears on the coils |
Room temperature is below 41°F (5°C) |
Please operate unit at temperatures above 41 F (5 C). Frost will usually disappear within 60 minutes. Under certainconditions, frost may appear on the coils of your dehumidifier at temperatures above 41 °F ( 5 °C ). This is normal and frost will usually disappear within 60 minutes. See the Automatic Defrost section . |
Fan noise |
Air is moving through the dehumidifier. |
This is normal. |
Water on floor |
Hose connection may be loose. |
Check the hose connection. See the Removing Collected Water section. |
Intended to use the bucket to collect water, but a hose was attached. |
Disconnect the hose if using a bucket to collect water. See the Removing Collected Water section. |
Bucket Full LED light flashing and alarm sounds while drain hose is connected. |
Drain hose not tight on fitting. |
Check drain hose connection. |
Drain hose is kinked. |
Ensure the drain hose is pointed straight down to the floor and is not kinked in anyway. |